Section 100.205(c)(3)(ii) requires that all covered multifamily dwellings with a building entrance on an accessible route shall be designed and constructed in such a manner that all premises within covered multifamily dwelling units contain light switches, electrical outlets, thermostats, and other environmental controls in accessible locations.
Guideline
Light switches, electrical outlets, thermostats and other environmental controls would meet section 100.205(c)(3)(ii) if operable parts of the controls are located no higher than 48 inches, and no lower than 15 inches, above the floor. If the reach is over an obstruction (for example, an overhanging shelf) between 20 and 25 inches in depth, the maximum height is reduced to 44 inches for forward approach; or 46 inches for side approach, provided the obstruction (for example, a kitchen base cabinet) is no more than 24 inches in depth. Obstructions should not extend more than 25 inches from the wall beneath a control. (See Fig.2.)
Note
Controls or outlets that do not satisfy these specifications are acceptable provided that comparable controls or outlets (i.e., that perform the same functions) are provided within the same area and are accessible, in accordance with this guideline for Requirement 5.
(a) Forward Reach Limit
NOTE: Clear knee space should be as deep as the reach distance.
(b) Maximum Forward Reach Over an Obstruction
(c) Maximum Side Reach Over Obstruction
Fig. 2 Reach Ranges
Source: 24 CFR Part 100—Fair Housing Accessibility Guidelines by U.S. Department of Housing and Urban Development (HUD), Office of the Assistant Secretary for Fair Housing and Equal Opportunity - published 03/06/1991